Emergency lighting requirements.

Emergency lighting is required under Article 14 of the Fire Safety Order wherever escape routes need illumination that survives a mains failure — in practice, almost all non-domestic premises and the common parts of residential buildings beyond the very simplest. The design standard is BS 5266-1, the normal benchmark is three-hour duration, and the testing regime is a monthly function test plus an annual full-duration test, both recorded.

Updated 9 July 2026 · England & Wales · Regulatory Reform (Fire Safety) Order 2005

Where it's required.

"Emergency routes and exits requiring illumination must be provided with emergency lighting of adequate intensity in the case of failure of their normal lighting."Article 14(2)(h), Regulatory Reform (Fire Safety) Order 2005

BS 5266-1 translates that duty into coverage. The fire risk assessment confirms the premises-specific extent, but the standard expects luminaires at the points where escape fails in darkness:

In small, simple premises with short, straight, borrowed-light escape routes, the assessment may justify limited provision; in sleeping-risk premises — hotels, larger HMOs, blocks of flats — full escape route coverage is the enforced norm, because escape happens at night by definition.

Design and duration choices.

ParameterOptionsStandard practice
Duration1 hour or 3 hours3 hours wherever premises are not evacuated immediately or may be reoccupied quickly — the default specification; sleeping premises always 3 hours
ModeMaintained (lit at all times) / non-maintained (lights on mains failure)Non-maintained in workplaces; maintained for exit signs and in premises open to the public in darkness (venues, cinemas, licensed premises)
IlluminancePer BS 5266-1 / BS EN 1838Minimum 1 lux along the centre line of escape routes; 0.5 lux in open-area cores; higher at high-risk tasks
ArchitectureSelf-contained luminaires / central batterySelf-contained dominates small and medium premises; central battery in larger estates for maintainability

Testing: the regime that gets checked.

These records are precisely what a fire risk assessor, an auditing officer and an insurer each ask to see — untested emergency lighting is one of the most common findings in office and residential assessments, and one of the cheapest to fix: the failure is administrative before it is electrical.

Key fact: Emergency lighting failures are invisible until the moment they matter — a dead battery looks identical to a charged one. The monthly key-switch test takes minutes per circuit and converts an unknowable risk into a logged, managed system.

Common questions.

Is emergency lighting a legal requirement in small premises?
Where the escape routes need illumination to be used safely in a mains failure, yes — Article 14 applies regardless of size. A small shop with a straight, short route and good borrowed light may justify minimal provision; the fire risk assessment records that judgement.
Do HMOs and blocks of flats need emergency lighting?
Larger and higher-risk HMOs and most blocks of flats, yes — escape routes used at night without borrowed light are exactly the target case. Two-storey shared houses with simple, naturally-lit routes may be assessed as not requiring it under LACORS-derived standards.
Who can test emergency lighting?
Monthly function tests can be done in-house by a trained person with a log book. The annual duration test and any remedial work should go to a competent electrical contractor, with certificates retained.
What's the difference between maintained and non-maintained fittings?
Maintained luminaires are lit continuously and stay lit on mains failure — required where the public occupies darkened spaces. Non-maintained fittings energise only when the mains fails — standard for workplaces.