Fire extinguisher requirements.

Article 13 of the Fire Safety Order requires premises to be equipped with appropriate firefighting equipment — in practice, portable extinguishers selected against the fire classes present, provided to BS 5306-8, sited on escape routes within 30 metres' travel of any fire risk, commissioned on installation and serviced annually. The fire risk assessment determines type, number and placement.

Updated 9 July 2026 · England & Wales · Regulatory Reform (Fire Safety) Order 2005

Types against fire classes.

ExtinguisherColour bandFire classesNever use on
Water / water mistRed / white bandA (solids: wood, paper, textiles)Live electrical, oils, fats
Foam (AFFF)CreamA, B (flammable liquids)Cooking oils; caution near live electrical
CO₂BlackB, electrical equipmentClass A deep-seated fires; confined spaces caution
Dry powderBlueA, B, C (gases), electricalIndoor use discouraged — visibility, inhalation, cleanup; not for Class F
Wet chemicalYellowF (cooking oils and fats), A—; the mandatory choice for commercial kitchens
Specialist lithium-ion agentsPer productLi-ion battery fires (emerging provision)Specified by risk assessment where battery risk is concentrated

How many, and where.

Commissioning, servicing, records.

Service labels and certificates join the alarm and emergency lighting records as the documentation trio every assessor, auditing officer and insurer requests.

"Where necessary... the responsible person must ensure that the premises are, to the extent that it is appropriate, equipped with appropriate fire-fighting equipment and with fire detectors and alarms."Article 13(1), Regulatory Reform (Fire Safety) Order 2005

Training and the first-aid firefighting decision

Extinguishers are first-aid equipment for nascent fires and for fighting a path to escape — nothing more. Article 21 training should cover which extinguisher for which risk and, above all, when not to fight: fire larger than a waste bin, smoke at ceiling level, or any doubt means evacuate. Some premises legitimately adopt an evacuate-only policy for staff; the assessment records that decision and provision is scaled accordingly — the equipment must still be present and maintained for escape-path protection.

Key fact: The commonest extinguisher findings are administrative: missing annual service, units on the floor behind stock, wrong type at the risk (water beside the fryer). Every one is visible in thirty seconds at audit — and every one is closed for the price of a service contract and a bracket.

Common questions.

How many fire extinguishers does my premises legally need?
The number the fire risk assessment determines against BS 5306-8 — the working baseline is two 13A-rated extinguishers per floor (26A combined) within 30m travel of any point, adjusted for size, layout and specific risks like kitchens and electrical rooms.
Do fire extinguishers need servicing every year?
Yes — an annual basic service by a competent technician to BS 5306-3, plus monthly in-house visual checks, extended service at five years and CO₂ overhaul at ten. The service label is the first thing an inspector reads.
Can staff be banned from using extinguishers?
A responsible person can adopt an evacuate-only policy where the assessment supports it, and provision is scaled to escape-path protection. What's not defensible is providing equipment and giving no Article 21 training on it.
What extinguisher covers computers and server rooms?
CO₂ for the electrical risk, paired with Class A cover nearby. Powder discharges are ruinous to electronics and discouraged indoors; fixed suppression is assessed case-by-case for critical server rooms.

Related guides

Right type, right place, in date.

Assessments that map extinguisher provision to BS 5306-8 — with a supply-and-service schedule you can act on immediately.